Home > Building Material Flammability Test Equipment > GJL-2 Steel-Structure-Fireproof-Coating-Sample-Testing-Furnace-(Fireproof-of-Plugging-Material)
GJL-2 Steel-Structure-Fireproof-Coating-Sample-Testing-Furnace-(Fireproof-of-Plugging-Material)
GJL-2 Steel-Structure-Fireproof-Coating-Sample-Testing-Furnace-(Fireproof-of-Plugging-Material)
GJL-2 Steel-Structure-Fireproof-Coating-Sample-Testing-Furnace-(Fireproof-of-Plugging-Material)
GJL-2 Steel-Structure-Fireproof-Coating-Sample-Testing-Furnace-(Fireproof-of-Plugging-Material)

GJL-2 Steel-Structure-Fireproof-Coating-Sample-Testing-Furnace-(Fireproof-of-Plugging-Material)

Product Model : GJL-2
Technical indicators 1. Operating Voltage: AC 380V +/-10% 50Hz ; Electric power: 3KW 2. Stove Pressure Measurement Range: 0-100Pa Measurement Accuracy: ≤ +/-3Pa 3. Air Flow: 0-50 m³/min Measurement Accuracy: ≤ +/-0.5 m³/min 4. Burning Airflow: Propane ,Liquefied gas 5. Gas Flow: 0-100 L/min Measurement Accuracy:2.5 level 6. Tank Capacity: 50 kg*2
Detailed description

Technical indicators
1. Operating Voltage: AC 380V +/-10% 50Hz ;  Electric power: 3KW
2. Stove Pressure Measurement Range: 0-100Pa Measurement Accuracy: ≤ +/-3Pa
3. Air Flow: 0-50 m³/min Measurement Accuracy: ≤ +/-0.5 m³/min
4. Burning Airflow: Propane ,Liquefied gas
5. Gas Flow: 0-100 L/min          Measurement Accuracy:2.5 level
6. Tank Capacity: 50 kg*2

7. Test Temperature : Program warming    60min room temperature-925
                                                  120min room temperature-1050

                                                  180min room temperature-1115

                                                   240min room temperature-1150

                                                   300min room temperature-1180

                                                   360min room temperature-1210

8.Equipment Precision: a.furnace temperature: +/-15

                           b.internal specimen temperature: +/-10

                           c.backfire specimen temperature: +/-4

9. Temperature Sensor:    a.armored platinum rhodium platinum value S thermocouple
                          accuracy class:II level
                               b.armored nickel-chromium nickel-silicon value K thermocouple
                          accuracy class:II level
10. Timing Range: 0-360 min                       Timing Accuracy: < +/-2s
11. Maximum of Burning Length of the Sample: 1600mm
12. Instrument Dimensions:          Test plate bracket      670mm*670mm*1100mm
                        
                               Control box              800mm*500mm*500mm

 

Features
1.PLC+NA view professional software, touch screen control, easy operation
2. The whole process of testing is fully automated
3. Temperature errors are lower than the national standard

 

Design Standards
GB14907-2002 Steel-Structure Fireproof Coating
GB T9978-2008 Fire Resistance Test Method for Building Components
GB T23864-2009 Plugging Material of Fireproof
Related products More>