Cone Calorimeter
Application
Suitable for testing the heat release rate of building materials.
Standard: ISO5660-1:2002
Technical Parameters
Power supply voltage | AC220V AC 50Hz |
Maximum operating power | ≥5KW |
Cone heater power | ≤5KW |
Heat output heat | 0~120KW/m2 |
The maximum placement of the sample box | 100mm × 100mm × 50mm |
Exhaust flow rate | 0.012m3/s~0.035 m3/s (adjustable) |
Timing value resolution | 1s error <1s/n |
Oxygen analysis | paramagnetic oxygen analyzer, concentration range 0-25% |
Smoke density analysis | (optional) |
Infrared analyzer | CO: 0-1% CO2: 0-10% (optional) |
Main feature
1. The test result data of SZL-1 cone calorimeter includes the following:
a. ignition time
b. Average heat release rate within 180s after ignition for 180s
c. total heat release (mj/m2)
d. Initial mass and residual mass (Kg) of the sample
2. f. Average mass loss (kg/s) after ignition to the end of the test
g. Radiation intensity (KW/M2) and displacement (m3/s)
h. heat release rate - time curve
i. smoke release rate (optional)
j. Toxic gas (carbon monoxide, carbon dioxide) (optional) generation rate (optional)
High voltage spark generator: automatic positioning ignition
Modular combination of equipment: Users can select the standard configuration according to the actual application;
Equipment dimensions: length × width × height (1.68 × 0.686 × 1.92) m;
Equipment weight: 350 Kg.
What is a cone calorimeter test?
A cone calorimeter is a device used to study the fire behavior of small samples of various materials in condensed phase. It is widely used in the field of Fire Safety Engineering. ... The Cone Calorimeter has long been considered the most significant bench scale instrument in the field of fire testing.